  • Switching between PU and NET operation modes

    Set Pr.340 (Communication startup mode selection) to "10".The operation mode can be switched between PU and NET by assigning X65 (PU-NET operation switching)... More Details >>

    • No:21878
    • Release Date:2018/08/22 16:29
  • Frequency setting

    No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>

    • No:21911
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can use it for inverter operation, but the running speed of the inverter does not change linearly with regard to turn of the frequency setting potentiome... More Details >>

    • No:21912
    • Release Date:2018/08/22 16:30
  • FR-PU04

    While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>

    • No:21919
    • Release Date:2018/08/22 16:30
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • Frequency setting signal

    Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>

    • No:21267
    • Release Date:2018/08/22 16:26
  • Parameter copy of FR-Configurator

    The parameter can be copied to only one inverter. More Details >>

    • No:21306
    • Release Date:2018/08/22 16:26
  • Supported model for FR-Configurator

    For the models other than FR-A700/F700, use FR-Configurator (FR-SW3-SETUP-WJ). They are not supported by FR-Configurator (FR-SW2-SETUP-WJ). When you have the... More Details >>

    • No:21313
    • Release Date:2018/08/22 16:26
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670
    • Release Date:2018/08/22 16:28