Operation of automatic restart after instantaneous power failure
1. No operation log is recorded.2. No. However, you can create a state indicating that automatic restart after instantaneous power failure is in progress by ... More Details >>
- No:21948
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
1. To perform emergency stop, it is recommended to have the motor coast and stop it using a mechanical brake.In this case, the output stop (MRS) signal is in... More Details >>
- No:22103
- Release Date:2018/08/22 16:31
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Refer to the following points.For fan pump -> Square torqueFor general-purpose machine (for example, transport, elevation) -> Constant-torque type More Details >>
- No:22048
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Operation of the motor with a brake
For the general-purpose inverter, the motor stop cannot be detected accurately because the actual motor speed from a motor is not input. In general, the RUN ... More Details >>
- No:21375
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
The FR-A500 series that is the successor of the FR-A200E series has a function similar to output current detection of the FR-E500. Consider using the FR-A500... More Details >>
- No:21453
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-A200
-
Inverter operation at instantaneous power failure
When performing the automatic restart after instantaneous power failure, input the operation signal (STF or STR) and selection of automatic restart after ins... More Details >>
- No:21371
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Since the brake sequence function requires Advanced magnetic flux vector control and advanced flux control is applied to 0.4 kW or higher motors, you cannot ... More Details >>
- No:22075
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Two-rank up maximum short-time torque
It is not possible to generate torque larger than the maximum possible torque of the motor by increasing the inverter's capacity.Even when the inverter is up... More Details >>
- No:22027
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Output phase loss protection error
- How to find out lost phaseMeasure the three-phase current when the error has occurred.The phase with a small (or no) phase current is lost.- Possibility of... More Details >>
- No:21969
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500