  • FR-RC

    Pr.30 = "1" and Pr.70 = "0". More Details >>

    • No:21143
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    With the automatic bypass sequence (Pr.139 ≠ 9999, Pr.159 = 9999), the motor operation is switched to commercial power supply operation when the output frequ... More Details >>

    • No:21189
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>

    • No:21190
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    The operation cannot be manually switched to the commercial power supply operation at an inverter fault. The operation can be automatically switched to the c... More Details >>

    • No:21191
    • Release Date:2018/08/22 16:26
  • Model selection

    Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>

    • No:21244
    • Release Date:2018/08/22 16:26
  • Operation method

    Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>

    • No:21249
    • Release Date:2018/08/22 16:26
  • FR-A7NC E kit

    Not available. Differences between the parts supplied with the FR-A7NC and FR-A7NC E kit will result in improper installation. Use the FR-A7NC. Use the FR-A7NC. More Details >>

    • No:21258
    • Release Date:2018/08/22 16:26
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Terminal indicator lamp

    The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>

    • No:21323
    • Release Date:2018/08/22 16:27
  • Fault output terminal A, B, and C

    Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>

    • No:21324
    • Release Date:2018/08/22 16:27