Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F700P ]

201-210 of Total 295

prev 21 / 30page next
  • Adjustment of analog gain

    Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>

    • No:21689
    • Release Date:2018/08/22 16:28
  • FR-DU07

    Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>

    • No:21708
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    No. You cannot check the accumulated number of rotations on the monitor.   More Details >>

    • No:21715
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29
  • Output current

    Increasing the value of Pr.0 (Torque boost) increases the output voltage, and the output current also increases.Note that increasing this value too high puts... More Details >>

    • No:21732
    • Release Date:2018/08/22 16:29
  • Frequency setting

    You can set the running frequency up to 400 Hz.It depends on the specifications of the motor used whether or not operation with a frequency of 120 Hz or high... More Details >>

    • No:21738
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This parameter cannot be changed in the external operation mode.Change Pr.77 (Parameter write selection) to "2" before changing the setting of Pr.72. More Details >>

    • No:21743
    • Release Date:2018/08/22 16:29
  • NET mode

    After setting Pr.340 to "10", you need to power OFF then ON the inverter to make the new setting enabled because you are setting the operation upon power-on.... More Details >>

    • No:21759
    • Release Date:2018/08/22 16:29
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • Minimum frequency

    If any other frequency is not set, when the start signal is input, the inverter starts acceleration from 0.5 Hz set with Pr.13 (Starting frequency) up to 3 H... More Details >>

    • No:21777
    • Release Date:2018/08/22 16:29

201-210 of Total 295

Inquiries