Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324
- Release Date:2018/08/22 16:27
-
For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>
- No:21348
- Release Date:2018/08/22 16:27
-
Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>
- No:21670
- Release Date:2018/08/22 16:28
-
If the values are already entered in the setting column, performing batch write reflects the setting on the inverter. More Details >>
- No:21709
- Release Date:2018/08/22 16:29
-
10 VDC voltage from terminal 10
Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>
- No:21727
- Release Date:2018/08/22 16:29
-
Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency). More Details >>
- No:21744
- Release Date:2018/08/22 16:29
-
Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>
- No:21833
- Release Date:2018/08/22 16:29
-
You also need to set Pr.79 (Operation mode) to "3". More Details >>
- No:21844
- Release Date:2018/08/22 16:29
-
The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>
- No:21858
- Release Date:2018/08/22 16:29
-
Set Pr.56 (Current monitor reference) to "10A". More Details >>
- No:21865
- Release Date:2018/08/22 16:29