Horizontal installation prevents heat release, resulting in a failure. Install the inverter vertically. More Details >>
- No:21286
- Release Date:2018/08/22 16:26
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
-
Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>
- No:21266
- Release Date:2018/08/22 16:26
-
The FR-A5AY cannot be used in the FR-A700 (F700(P)). It cannot be installed due to the difference of the connector shape. More Details >>
- No:21260
- Release Date:2018/08/22 16:26
-
Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>
- No:21257
- Release Date:2018/08/22 16:26
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
-
Since the initial value of Pr.13 (Starting frequency) is 0.5 Hz, the operation does not start unless 0.5 Hz or higher frequency is set. When 0.49 Hz is set i... More Details >>
- No:21251
- Release Date:2018/08/22 16:26
-
Set Pr.79 (Operation mode) to "3" and Pr.161 (Frequency setting/key lock operation selection) to "1". More Details >>
- No:21249
- Release Date:2018/08/22 16:26
-
It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>
- No:21247
- Release Date:2018/08/22 16:26