FAQ within [ FREQROL-F700P ]

281-290 of Total 294

prev 29 / 30page next
  • 4 to 20 mA output

    Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>

    • No:21246
    • Release Date:2018/08/22 16:26
  • Brake resistor

    Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>

    • No:21330
    • Release Date:2018/08/22 16:27
  • CC-Link

    Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>

    • No:21899
    • Release Date:2018/08/22 16:29
  • CC-Link

    The FR-A7NC is required. ("FR-A7NC-E kit" for the FR-E700 series. The FR-E700-NC CC-Link communication type does not require an option.) More Details >>

    • No:21668
    • Release Date:2018/08/22 16:28
  • AM terminal output

    Set Pr.55 (Frequency monitoring reference) of the first inverter to 70 Hz. More Details >>

    • No:21257
    • Release Date:2018/08/22 16:26
  • Changing the control method

    Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>

    • No:21245
    • Release Date:2018/08/22 16:26
  • CC-Link

    You can use it with the 700 series inverters. Note that the installation method of the card differs for the FR-E700 series and FR-A700/F700 series.If you hav... More Details >>

    • No:21887
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.338 (Operation command source) to "1" (external terminal).Set Pr.339 (Speed command source) to "0" (communication).Check the setting of Pr.79 for oper... More Details >>

    • No:21869
    • Release Date:2018/08/22 16:29
  • Electronic bypass function

    The signals MRS and CS are required when the automatic bypass sequence enabled. More Details >>

    • No:21187
    • Release Date:2018/08/22 16:26
  • Start command, speed command

    You can do so by setting Pr.339 (Communication speed command source) = 1 (external).   More Details >>

    • No:21881
    • Release Date:2018/08/22 16:29