As described in the instruction manual, use the shielded cable or twisted cable to avoid the influence of noises. More Details >>
If "PS" is displayed even the "STOP/RESET" key on the operation panel is not pressed, a inverter fault may be the cause. In this case, consult with your sale... More Details >>
There is no problem with the wiring. Keep the rating (24 VDC, 0.1 A) of the terminal PC. More Details >>
For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
The detection time 1 s cannot be changed. More Details >>
Yes.Set Pr.19 (Base frequency voltage) to "200 V".200 V output will be obtained during 60 Hz operation. More Details >>
Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>