You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
-
Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>
- No:21903
- Release Date:2018/08/22 16:30
-
Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>
- No:21909
- Release Date:2018/08/22 16:30
-
You can connect up to three inverters to a single external frequency setting potentiometer to control them. More Details >>
- No:21917
- Release Date:2018/08/22 16:30
-
It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>
- No:21180
- Release Date:2018/08/22 16:26
-
For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>
- No:21188
- Release Date:2018/08/22 16:26
-
Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>
- No:21190
- Release Date:2018/08/22 16:26
-
Set Pr.71 (Applied motor), Pr.80 (Motor capacity), Pr.81 (Number of motor poles), and Pr.800 (Control method selection). More Details >>
- No:21245
- Release Date:2018/08/22 16:26
-
The station number and baud rate were set using the dial for the FR-A5NC, but parameter is used for the FR-A7NC. Pr.542 (Communication station number (CC-Lin... More Details >>
- No:21248
- Release Date:2018/08/22 16:26