The calibration parameter C6 (Terminal 4 frequency setting bias) is initially set to "20%". Therefore, voltage input to the terminal 4 does not become effect... More Details >>
- No:21806
- Release Date:2018/08/22 16:29
-
1. Use the external terminals STF, RL, and SD. (A push-ON switch for operation is required between the terminals STF and SD, and a push-OFF switch is require... More Details >>
- No:21816
- Release Date:2018/08/22 16:29
-
No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>
- No:21911
- Release Date:2018/08/22 16:30
-
While the FR-PU04 does not display parameter names, it displays parameter numbers and you can set them. More Details >>
- No:21919
- Release Date:2018/08/22 16:30
-
Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>
- No:21270
- Release Date:2018/08/22 16:26
-
Calibrate the terminal 2 bias. More Details >>
- No:21281
- Release Date:2018/08/22 16:26
-
Parameter copy of FR-Configurator
The parameter can be copied to only one inverter. More Details >>
- No:21306
- Release Date:2018/08/22 16:26
-
Supported model for FR-Configurator
For the models other than FR-A700/F700, use FR-Configurator (FR-SW3-SETUP-WJ). They are not supported by FR-Configurator (FR-SW2-SETUP-WJ). When you have the... More Details >>
- No:21313
- Release Date:2018/08/22 16:26
-
Supported model for FR-Configurator
The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>
- No:21314
- Release Date:2018/08/22 16:26
-
Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324