  • Items controllable via CC-Link

    1. Not all items can be controlled.   - Functions that cannot be controlled JOG, AU, CS, OH, X10, X11, X12, and X16 functions (Other functions can be control... More Details >>

    • No:21459
    • Release Date:2018/08/22 16:27
  • Noise from motor at low speed

    It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>

    • No:21428
    • Release Date:2018/08/22 16:27
  • Operation command terminal switching

    It rotates in the forward direction while STF is ON.And then, when STR is turned ON and STF is turned OFF, the inverter decelerates down to 0 Hz within the s... More Details >>

    • No:22070
    • Release Date:2018/08/22 16:30
  • Communication operation with FR-E500

    We have no sample program for RS485 communication. Since the communication method of the FR-SW0-SETUP uses a different protocol from 485 communication and st... More Details >>

    • No:21451
    • Release Date:2018/08/22 16:27
  • Inverter input power supply

    Square wave input is not recommended since it can cause failures (for example, damage the diode bridge). More Details >>

    • No:22106
    • Release Date:2018/08/22 16:31
  • RS485 communication

    The RS485 communication is explained in the FREQROL-E500 Instruction Manual. This Instruction Manual is published on the member's page of Mitsubishi Electric... More Details >>

    • No:21426
    • Release Date:2018/08/22 16:27
  • Driving 200 V motor by 400 V inverter

    Your suggested use is not recommended due to the following reasons: Output voltage of the 400 V inverter contains "micro surge". Usually this surge voltage i... More Details >>

    • No:21403
    • Release Date:2018/08/22 16:27
  • Clutch connection of load

    Since a large load is applied to the motor when the electromagnetic clutch turns on, overcurrent may occur if the load is heavy. To ensure that the rated cur... More Details >>

    • No:21955
    • Release Date:2018/08/22 16:30
  • External thermal overheat

    Take the following countermeasure:1. If the thermal trips in low-speed operation, trips can be avoided, depending on the external thermal relay operation cha... More Details >>

    • No:21954
    • Release Date:2018/08/22 16:30
  • Operation frequency

    I cannot answer clearly because the load is unknown. The operation cycle of operating for 10 seconds and stopping for 10 seconds is OK, but it is questionabl... More Details >>

    • No:21474
    • Release Date:2018/08/22 16:27