It is said that the EEPROM has a lifetime of 100,000 write cycles. When the data is written every time the frequency changes, the life of the EEPROM may not ... More Details >>
- No:20996
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800 , FREQROL-E700 , FREQROL-D700
-
No, it is not available. It is only available in the External operation mode or combined operation mode (PU speed command and External operation command (Pr.... More Details >>
- No:21192
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>
- No:21792
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
How can I have the motor coast to stop?
You can use the following two methods:1. Turn ON MRS at the same time when STF turns OFF.2. Set Pr.10 = 60 Hz, Pr.11 = 0 sec, and Pr.12 = 0% (when the invert... More Details >>
- No:21967
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Impossible to recover after power failure
First, ensure that the parameter for automatic restart after instantaneous power failure is set correctly and then do the following:1. Check if the terminals... More Details >>
- No:22033
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Relationship between rotary switch and axis number
When the rotary switch is “0”, the 1st axis and is “1”, the 2nd axis. When the rotary switch is “A”, the 11th axis and is “F”, the 16th axis. In combination ... More Details >>
- No:23644
- Release Date:2018/09/14 15:10
- Category: MELSERVO-J4
-
Depending on each cable. Refer to each SSCNET III/H compatible servo amplifier instruction manual. More Details >>
- No:23652
- Release Date:2018/09/14 15:10
- Category: MELSERVO-J4 , MELSERVO-JE
-
For the inverter with capacity of 160K or higher, the fuse is built in its DC part. More Details >>
- No:20940
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options
-
It is the brake function that consumes the rotational energy by heat and stops the motor immediately by short-circuiting between the motor terminals through ... More Details >>
- No:21066
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Others
-
The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>
- No:21068
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Options , FREQROL-A800 , FREQROL-A700